Specifications
Power
• Input: 120-240 V~ 50/60 Hz 10 A
• Each output: 35 V- 143 mA 5 W
• Each output is capable of powering one Sivoia QS shade or drapery drive unit, OR up to 8 QS PDUs; see Wiring Rules
Input Wiring
• 14 AWG – 10 AWG (2.5 mm2 -4.0 mm2
) single wire, solid or stranded
• Torque terminal screws to: 5 in-lbs (0.5 N•m)
• Strip length: 5
⁄16 in (8 mm)
• Maximum 1 panel per 15 A circuit breaker (limiting factor is inrush current)
• Maximum 2 panels per 20 A circuit breaker (limiting factor is inrush current)
Output Terminal Wiring
• 22 AWG–12 AWG (0.5 mm2-4.0 mm2) single wire, solid or stranded (wire gauge affects allowable length of run; see Wiring Rules)
• Torque terminal screws to: 5 in-lbs (0.5 N•m)
• Strip length: 1
⁄4 in (6 mm)
• Ten (10) output terminals for shade power/communication (4-conductor)
• Two (2) link terminals for communication pass-through (3-conductor)
Previous product
Back to products
LOS C Series Wired Sensors
300.00 CHF HT
Next product
QS-WLB
116.87 CHF HT
QSPS-10PNL
2298.00 CHF HT
QSPS-10PNL: 10-Output Smart Panel
Description
Additional information
Weight | 1 kg |
---|